Main camp product:Hall Open-loop current sensor  Hall closed-loop current senso  Hall Voltage Sensor  Magnet DC Current Sensor  
[

TBC-E

]
sendmsg
ProductName: TBC-E
ProductModel: Output Voltage
ProductManufacturer: Hall current sensor / CHINA HALL
ProductSimpleIntroduce
The TBC-E series current sensor is a closed loop device based on the principle of the hall effect and null balance method.The output from the current sensor is the balancing current which is a perfect image of the primary current reduced by the number of secondary turns at any time.This current can be expressed as a voltage by passing it through a resister.It provides accurate electronic measurement of DC,AC or pulsed currents


TBC-E  detail

TBC-E Series Hall Effect Current Sensor
DESCRIPTION
The TBC-E series current sensor is a closed loop device based on the principle of the hall effect and null balance method.The output from the current sensor is the balancing current which is a perfect image of the primary current reduced by the number of secondary turns at any time.This current can be expressed as a voltage by passing it through a resister.It provides accurate electronic measurement of DC,AC or pulsed currents.
 
ELECTRICAL DATA
 
Type
TBC50E                    
TBC75E
TBC100E
TBC200E
TBC300E
 
Rated current(Ip)
50
75
100
200
300
A
Measure range
120
200
250
450
550
A
Turns ratio
1:1000
1:1500
1:1000
1:2000
1:3000
 
Measurement of internal resistance
80±0.1%
80±0.1%
40±0.1%
40±0.1%
40±0.1%
 
Rated output
 
 
4±0.5%
V
Supply voltage
 
 
±15 ±5%
V
Offset Voltage
 
 
10
mV
Offset voltage drift
 
 
≤±0.5
mV/℃
Linearity
 
 
0.1
%FS
Response time
 
 
≤1
μS
Galvanic isolation
50HZ,1min
 
3.0
KV
Operating temperature
 
 
-40~+85
Storage temperature
 
 
-40~+125
 
MUTING DIMENSIONS(FOR REFERENCE ONLY)

DIRECTIONS FOR USE
1.Is will be in a forward direction when the Ip flows according to the direction of the arrowhead.
2.The primary conductor should be≤120℃;
3.The dynamic performance (di/dt and the response time)is the best when the primary hole is fully filled with the bus bar.
4.The primary turns should be at the top of the sensor for the best magnetic coupling.


Leave a message for product


Hall current sensor / CHINA HALL
Tel :025-84311092    Fax:025-84372728
Address:The westen zone of 5311plant , Biao Yin No.4#. Nanjing City, Jiangsu Provice, P.R.C.  
粤ICP备08118721号   SiteAdmin